Calculation of the Impedances
6.2.3.1
Method of Operation
A separate measuring system is provided for each of the six possible impedance loops
L1–E, L2–E, L3–E, L1–L2, L2–L3, L3–L1. The phase-earth loops are evaluated when
an earth fault detection according to section 6.2.1 is recognized and the phase current
exceeds a settable minimum value
Minimum Iph>
(address
1202
). The phase-
phase loops are evaluated when the phase currents in both of the affected phases ex-
ceed the minimum value
Minimum Iph>
.
A jump detector synchronizes all the calculations with the fault inception. If a further
fault occurs during the evaluation, the new measured values are immediately used for
the calculation. The fault evaluation is therefore always done with the measured val-
ues of the current fault condition.
Phase–Phase
Loops
To calculate the phase-phase loop, for instance during a two-phase fault L1–L2 (Fig-
ure 6-22), the loop equation is:
where
U,
I
are the (complex) measured values and
Z = R+ jX is the (complex) line impedance.
The line impedance is computed to be
Figure 6-22
Short circuit of a phase-phase loop
The calculation of the phase-phase loop does not take place as long as one of the con-
cerned phases is switched off (during single-pole dead time), to avoid an incorrect
measurement with the undefined measured values existing during this state. A state
recognition (refer to Section 6.22) provides the corresponding block signal. A logic
block diagram of the phase-phase measuring system is shown in Figure 6-23.
I
L1
Z
L
I
L2
Z
L
U
L1–E
U
L2–E
–
=
⋅
–
⋅
Z
L
U
L1–E
U
L2–E
–
I
L1
I
L2
–
--------------------------------------
=
I
L1
I
L2
Z
L
Z
L
L1
L2
L3
E
U
L2–E
U
L1–E
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...