Functions
6-77
7SA6 Manual
C53000-G1176-C156-2
6.3.2
Applying the Function Parameter Settings
The power swing supplement is only active if it has been set to
Power Swing
=
En-
abled
(address
120
) during the configuration.
The four possible programs may be set in address
2002
P/S Op. mode
, as de-
scribed in Sub-section 6.3.1:
All zones block
or
Z1/Z1B block
or
Z2 to Z5
block
or
Z1,Z1B,Z2 block
.
Additionally the tripping function for unstable oscillations (out-of-step condition, loss of
system synchronism) can be set with parameter
PowerSwing trip
(address
2006
),
which should be set to
Yes
if required (presetting is
No
). In the event of power swing
tripping it is sensible to set
P/S Op. mode
=
All zones block
for the power swing
blocking, to avoid premature tripping by the distance protection.
6.3.3
Settings
6.3.4
Information Overview
Addr.
Setting Title
Setting Options
Default Setting
Comments
2002
P/S Op. mode
all zones blocked
Z1/Z1B blocked
Z2 to Z5 blocked
Z1,Z1B,Z2 blocked
all zones blocked
Power Swing Operating mode
2006
PowerSwing trip
NO
YES
NO
Power swing trip
F.No.
Alarm
Comments
4164
Power Swing
Power Swing detected
4166
Pow. Swing TRIP
Power Swing TRIP command
4167
Pow. Swing L1
Power Swing detected in L1
4168
Pow. Swing L2
Power Swing detected in L2
4169
Pow. Swing L3
Power Swing detected in L3
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...