Functions
6-154
7SA6 Manual
C53000-G1176-C156-2
6.8.3
Settings
Addresses which have an „A“ attached to its end can only be changed with DIGSI
®
4
in “Additional Settings“.
Addr.
Setting Title
Setting Options
Default Setting
Comments
3201
FCT Telep. E/F
ON
OFF
ON
Teleprotection for Earth Fault O/
C
3202
Line Config.
Two Terminals
Three Terminals
Two Terminals
Line Configuration
3203A
Send Prolong.
0.00..30.00 sec
0.05 sec
Time for send signal prolonga-
tion
3207A
Delay for alarm
0.00..30.00 sec
10.00 sec
Unblocking: Time Delay for
Alarm
3208
Release Delay
0.000..30.000 sec
0.000 sec
Time Delay for release after pik-
kup
3209A
TrBlk Wait Time
0.00..30.00 sec;
∞
0.04 sec
Transient Block.: Duration exter-
nal flt.
3210A
TrBlk BlockTime
0.00..30.00 sec
0.05 sec
Transient Block.: Blk.T. after ext.
flt.
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...