Functions
6-186
7SA6 Manual
C53000-G1176-C156-2
F1
(address
3011
) of the c.t. with its associated current
CT Err. I1
(address
3010
)
as well as a further c.t. operating point
CT Err. F2
/
CT Err. I2
(address
3013
and
3012
), above which the angle displacement remains practically constant (see Figure
6-100), are set. The relay then approximates, with adequate accuracy, the character-
istic of the transformer. In isolated networks this angle error compensation is not nec-
essary.
Figure 6-100 Settings for the phase angle correction
6.13.3 Settings
Note:
The indicated secondary current values refer to current input I
4
. They are inde-
pendent from the nominal value of the device.
∆ϕ
I
F2
F1
I1
I2
Addr.
Setting Title
Setting Options
Default Setting
Comments
3001
Sens. Earth Flt
Alarm Only
ON
OFF
Alarm Only
Sensitive Earth Flt.(comp/ isol.
starp.)
3002
3U0>
1..150 V
50 V
3U0> pickup
3003
Uph-e min
10..100 V
40 V
Uph-e min of faulted phase
3004
Uph-e max
10..100 V
75 V
Uph-e max of healthy phases
3005
3I0>
0.003..1.000 A
0.050 A
3I0> Release directional ele-
ment
3006
T Sens.E/F
0.00..320.00 sec
1.00 sec
Time delay for sens. E/F detec-
tion
3007
T 3U0>
0.00..320.00 sec
0.00 sec
Time delay for sens. E/F trip
3008A
TRIP Direction
Forward
Reverse
Non-Directional
Forward
Direction for sens. E/F trip
3010
CT Err. I1
0.003..1.600 A
0.050 A
Current I1 for CT Angle Error
3011
CT Err. F1
0.0..5.0
°
0.0
°
CT Angle Error at I1
3012
CT Err. I2
0.003..1.600 A
1.000 A
Current I2 for CT Angle Error
3013
CT Err. F2
0.0..5.0
°
0.0
°
CT Angle Error at I2
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...