Functions
6-222
7SA6 Manual
C53000-G1176-C156-2
Synchronism
Check Conditions
before Automatic
Reclosure
Addresses
3510
to
3519
are relevant to the check conditions before automatic reclos-
ure of the circuit breaker. When setting the parameters for the internal automatic re-
closing function (Section 6.14.2) it was decided with which automatic reclosing cycle
synchronism and voltage check should be carried out.
Address
3510
Op.mode with AR
determines whether closing under asynchronous
system conditions is allowed. Set this parameter to
with T-CB close
, if asynchro-
nous closing shall be allowed; the relay will then consider the circuit breaker closing
time before determining the correct instant for the closing command. Remember that
closing under asynchronous system conditions is allowed only if the circuit breaker
closing time is set correctly (see above under Preconditions)! If you wish to permit au-
tomatic reclosure only under synchronous system conditions, set this address to
w/o T-CB close
.
The permissible magnitude difference of the voltages is set under address
3511
Max.
Volt. Diff
. Setting is in volts secondary. When operating the device from a person-
al computer using DIGSI
®
4, setting may be in secondary or primary values. Depend-
ing on the connection of the bus-bar voltage (phase–phase or phase–earth) the
phase–phase or the phase–earth voltage is decisive.
The permissible frequency difference between the voltages is set under address
3512
Max. Freq. Diff
, the permissible phase angle difference under address
3513
Max. Angle Diff
.
The further release conditions for automatic reclosing are set under addresses
3515A
to
3519
:
3515A
SYNC-CHECK
= synchronism check: the bus-bar (Ubus) and the
feeder (Uline) must both be live (
Live Volt.
Thr.
, address
3503
); the conditions for synchro-
nism
Max. Volt. Diff
(address
3511
),
Max.
Freq. Diff
(address
3512
), and
Max. Angle
Diff
(address
3513
) are checked before automatic
reclosure;
3516
Usync> U-line<
= dead-line check: the bus-bar (Ubus) must be live
(
Live Volt. Thr.
, refer to address
3503
), the
feeder (Uline) must be dead (
Dead Volt. Thr.
,
refer to address
3502
);
3517
Usync< U-line>
= dead-bus check: the bus-bar (Ubus) must be dead
(
Dead Volt. Thr.
, refer to address
3502
), the
feeder (Uline) must be live (
Live Volt. Thr.
, re-
fer to address
3503
);
3518
Usync< U-line<
= dead-bus and dead-line check: the bus-bar (Ubus)
and the feeder (Uline) must both be dead (
Dead
Volt. Thr.
, refer to address
3502
);
3519
OVERRIDE
=
automatic reclosure is released without any check.
The five possible release conditions are independent of each other and can be com-
bined.
Synchronism
Check Conditions
before Manual
Closing
The release conditions for manual closing are set under addresses
3530
to
3539
.
When setting the general protection data (Power System Data 2, Section 6.1.3) it was
decided whether synchronism and voltage check should be carried out before manual
closing. With the following setting in address
1151
MAN. CLOSE
=
w/o Sync-
check
, no checks are performed before manual closing. The following parameters are
then irrelevant.
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...