Functions
6-225
7SA6 Manual
C53000-G1176-C156-2
6.15.4 Information Overview
Important information available as output by the device is explained, in so far as it can
not be interpreted in the following list and was not described in the foregoing text.
„
>Sync. Start MC
“ (F.No. 2905)
Binary input which enables direct tripping of the sychnonism check with setting
parameters for manual close. This tripping with setting parameter for manual close
has always precedence if binary inputs „
>Sync. Start MC
“ (F.No. 2905) and
„
>Sync. Start AR
“ (F.No. 2906, see below) are activated at the same time.
“
>Sync.Start
” (F.No. 2906)
Request to execute a check synchronism measurement from an external automatic
reclosure device. After this request, the conditions for automatic reclosure are
checked.
“
Sync. release
” (F.No. 2951)
Release signal to an external automatic reclosure device.
.
3538
MC Usyn< Uline<
YES
NO
NO
Dead bus / dead line check
before Man.Cl
3539
MC O/RIDE
YES
NO
NO
Override of any check before
Man.Cl
Addr.
Setting Title
Setting Options
Default Setting
Comments
F.No.
Alarm
Comments
2901
>Sync. on
>Switch on synchro-check function
2902
>Sync. off
>Switch off synchro-check function
2903
>BLOCK Sync.
>BLOCK synchro-check function
2905
>Sync. Start MC
>Start synchro-check for Manual Close
2906
>Sync. Start AR
>Start synchro-check for AR
2907
>Sync. synch
>Sync-Prog. Live bus / live line / Sync
2908
> Usyn< U-line>
>Sync-Prog. Dead bus / live line
2909
> Usyn> U-line<
>Sync-Prog. Live bus / dead line
2910
> Usyn< U-line<
>Sync-Prog. Dead bus / dead line
2911
>Sync. o/ride
>Sync-Prog. Override ( bypass )
2930
Sync. on/off BI
Synchro-check ON/OFF via BI
2931
Sync. OFF
Synchro-check is switched OFF
2932
Sync. BLOCK
Synchro-check is BLOCKED
2934
Sync. faulty
Synchro-check function faulty
2935
Sync.Tsup.Exp
Synchro-check supervision time expired
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...