Functions
6-292
7SA6 Manual
C53000-G1176-C156-2
6.22
Function Control
The function control is the control centre of the device. It coordinates the execution of
the protection and supplementary functions, processes their decisions and the infor-
mation that emanates from the plant. In particular the following
•
switch-in recognition,
•
processing of the circuit breaker position,
•
fault detection logic,
•
tripping logic.
6.22.1 Detection of Line Energization
During energization of the protected object, several measures may be required or de-
sirable. Following a manual close onto a short-circuit, immediate trip of the circuit
breaker is usually required. In the Distance Protection for example, this is implement-
ed by activation of the overreaching zone Z1B for a short period following manual clo-
sure. The high-current switch-on-to-fault protection in particular is intended to trip im-
mediately following energization of a feeder on to a fault (refer to Sub-section 6.12.1).
In addition at least one stage of each short-circuit protection function can be selected
to trip without time delay following manual closure as described in the corresponding
sections. In this regard refer also to Sub-section 6.1.3 under the margin heading “Cir-
cuit Breaker Status”.
The manual close command must be routed to the device via a binary input. In order
to be independent of the duration that the switch is closed, the command is set to a
defined length in the device (adjustable with the address
1150A
SI Time Man.Cl
).
Fig. 6-148 shows the logic diagram.
Figure 6-148 Logic diagram of the manual closure handling
If the device has an integrated automatic reclosure, the integrated manual closure log-
ic of the 7SA6 automatically distinguishes between an external control command via
the binary input and an automatic reclosure by the internal auto-reclosure function so
that the binary input “
>Manual Close
” can be connected directly to the control circuit
of the close coil of the circuit breaker.
If, however, external close commands which should not activate the manual close
function are possible (e.g. external reclosure device), the binary input “
>Manual
Close
” must be triggered by a separate contact of the control switch (Figure 6-150).
&
>Manual Close
1150
> Manual Close
AR CLOSE Cmd.
FNo 2851
FNo 356
T
FNo 561
SI Time Man. Cl
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...