Functions
6-313
7SA6 Manual
C53000-G1176-C156-2
but also consumes storage capacity during the auto-reclosure dead time(s). This set-
ting can only be modified with DIGSI
®
4 under “Additional Settings”.
The actual storage time encompasses the pre-fault time
PRE. TRIG. TIME
(address
411
) ahead of the reference instant, the normal recording time and the post-fault time
POST REC. TIME
(address
412
) after the storage criterion has reset. The maximum
permissible storage period per fault recording
MAX. LENGTH
is set in address
410
.
The fault recording can also be triggered via a binary input, via the keypad on the front
of the device or with a PC via the operation or service interface. The storage is then
dynamically triggered. The length of the fault recording is set in address
415
BinIn
CAPT.TIME
(maximum length however is
MAX. LENGTH
, address
410
)
. The pre-
and post-fault times are additive. If the time for the binary input is set to
∞
, the duration
of the storage is as long as the binary input is initiated (static), the maximum length
however still is
MAX. LENGTH
(address
410
).
6.23.5 Settings
Addresses which have an „A“ attached to its end can only be changed with DIGSI
®
4
in “Additional Settings“
Average
Calculation
Min/Max Values
Addr.
Setting Title
Setting Options
Default Setting
Comments
2801
DMD Interval
15 Min per., 1 Sub
15 Min per., 3 Subs
15 Min per., 15 Subs
30 Min per., 1 Sub.
60 Min per., 1 Sub.
60 Min per., 1 Sub. Demand Calculation Intervals
2802
DMD Sync.Time
On the Hour
15 Min. after Hour
30 Min. after Hour
45 Min. after Hour
On the Hour
Demand Synchronization Time
Addr.
Setting Title
Setting Options
Default Setting
Comments
2811
MinMax cycRESET
NO
YES
YES
Automatic Cyclic Reset Function
2812
MiMa RESET TIME
0..1439 min
0 min
MinMax Reset Timer
2813
MiMa RESET-
CYCLE
1..365 day(s)
7 day(s)
MinMax Reset Cycle Period
2814
MinMax-
RES.START
1..365 Days
1 Days
MinMax Start Reset Cycle in
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...