Control During Operation
7-8
7SA6 Manual
C53000-G1176-C156-2
The inception of a fault is identified with the date and time in hours, minutes, and sec-
onds (resolution to ms). See the example in Figure 7-7.
The individual messages that are associated with the fault are tagged with a relative
time. At least one complete individual message always appears in the display.
Figure 7-7
Example of fault messages in the front display
Use the
and
keys to move up and down in the fault messages.
Use the
key to move back into the
TRIP LOG
level; or press the
key to go back
to the
MAIN MENU
.
From PC with
DIGSI
®
4
Click on
Annunciation
. The options appear in the data window (see Figure 7-2).
Double click on the desired message group in the data window, in this case the
Trip
Log
. A list appears in the data window, as shown in Figure 7-8.
By double clicking on an entry in the list view, the associated contents of the network
fault is displayed in another window. The entries are chronologically listed with the
newest message appearing first.
Figure 7-8
Selection of fault messages in DIGSI
®
4 — example
TRIP LOG 01/08
---------------------
>
Last Fault –> 1
>
2nd Last Fault –> 2
etc
LAST FAULT 01/10
---------------------
06/22 23:49:34,845
Network Fault 6 ON
MENU
:
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...