Control During Operation
7-21
7SA6 Manual
C53000-G1176-C156-2
7.1.3.2
Energy
Reading out
Metered Values
In the maximum scope of device 7SA6 there are counters that summarize the active
and reactive power (
Wp, Wq
) separately according to output and input of the active
energy or capacitive and inductive reactive power (in direction to the protected object).
It is a prerequisite that the direction is configured to
forward
(Address
201
, see Sec-
tion 6.1).
From the
DeviceFront
With the device ready for operation, first press the
key. The
MAIN MENU
appears.
Use the
key to select the menu item
Measurement
(See Figure
7-1), and switch
to the list of measured values using the
key. The
MEASUREMENT
selection appears.
There, select the menu item
Energy
with the
key, and switch to the table of energy
using the
key.
Use the
and
keys to move up and down in the table of the energy.
Use the
key to return to the
MEASUREMENT
submenu. Use the
key to return to
the
MAIN MENU
.
From PC with
DIGSI
®
4
Make a double click on
MEASUREMENT
(Figure 7-2) to view the measurement groups.
Select
Othe
r
with another double click.
In the next level double-click on
Energy
.
By double-clicking on an item in the list in the right part of the window, another window
is opened viewing the corresponding content of the counter group.
7.1.3.3
Setting Set Points
SIPROTEC
®
7SA6 enables the user to set limit points (or: set points) for some impor-
tant measured and metered values. If one of these set points is reached, exceeded or
undershot, the device generates an event log. This annunciation - like all event logs -
can be allocated to LEDs and/or output relays and then transmitted via interfaces.
Set points can be set for the following measured and metered values:
•
IL1dmd>: exceeding a preset maximum average value in phase L1.
•
IL2dmd>: exceeding a preset maximum average value in phase L2.
•
IL3dmd>: exceeding a preset maximum average value in phase L3.
•
I1dmd>: exceeding a preset maximum average value of the positive sequence sys-
tem of the currents.
•
|Pdmd|>: exceeding a preset maximum average value of the active power magni-
tude.
•
|Qdmd|>: exceeding a preset maximum average value of the reactive power mag-
nitude.
•
Sdmd>: exceeding a preset maximum average value of the apparent power.
•
|cos
ϕ
|<: untershooting a preset rate of the power factor
MENU
MENU
:
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...