Control During Operation
7-54
7SA6 Manual
C53000-G1176-C156-2
The Interlock display has an object table similar to the one described for Set Status.
The table provides the set interlocking conditions, which prevent, or could prevent, a
local control operation. Letters identify the interlocking conditions. The meanings of
the letters are:
•
L
Local/Remote (Switching Authority),
•
S
Equipment is subject to System Interlocking (in Substation Controller). Com-
mands entered locally are sent to the central computer or controller,
•
Z
Zone controlled (Field- or Bay-Interlocking),
•
P
Check switch position (test actual vs. scheduled),
•
B
Blocking by picked-up protection elements,
•
–
Non-Interlocked.
From PC with
DIGSI
®
4
With a device ready for operation, first press the
key. The
MAIN MENU
appears.
Using the
key, select the menu item
Control
and move to editing the control func-
tions with the
key. The selection
CONTROL
appears.
Select the item
Interlock
with the
key and switch to the next selection using the
key. The selection
INTERLOCK
appears. See Figure 7-55.
Figure 7-55
Ex
ample of Interlocking Conditions for Switching Equipment, Front Panel
From PC with
DIGSI
®
4
Interlocking is set for each switching device during project planning (see Sub-section
5.2.4) using the matrix and the dialog box “Object Properties”. Readout of the actively
set interlocking is always possible, across the entire path, without a password.
If the
Online
window in DIGSI
®
4 is opened with a double click, the operating func-
tions for the device appear in the left part of the window (Figure 7-35). Double clicking
on
Settings
brings up the function selection in the right side of the window. By dou-
ble clicking on
Masking I/O
, the matrix is opened. Mark the switching device (in the
line for the operating message of the switching device). Using the right mouse key, the
properties of the switching device can now be called up. The conditions for
Inter-
lock Switching
, among other items, are recognizable in the dialog box that opens.
Active test conditions are identified with a check mark.
:
MENU
INTERLOCK 01/03
--------------------
>
52Breaker L – Z P B
>
DiscSwit. L – Z P B
CONTROL 03/03
--------------------
>
Tagging –> 2
>
>
Interlock –> 3
1. 2. 3. 4. 5. Col-
GndSwit. L – Z P B
:
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...