Installation and Commissioning
8-46
7SA6 Manual
C53000-G1176-C156-2
G
At the terminals of the device, check continuity for each pair of terminals that re-
ceives current from the CTs.
G
Firmly re-insert the C–I/O–2 board. Carefully connect the ribbon cable. Do not bend
any connector pins! Do not use force!
G
Check continuity for each of the current terminal-pairs again.
G
Attach the front panel and tighten the screws.
o
Connect an ammeter in the supply circuit of the power supply. A range of about 2.5 A
to 5 A for the meter is appropriate.
o
Close the protective switches to apply voltage to the power supply. Check the polarity
and magnitude of the voltage at the device terminals.
o
The measured steady-state current should correspond to the quiescent power con-
sumption of the device. Transient movement of the ammeter merely indicates the
charging current of capacitors.
o
Remove the voltage from the power supply by opening the protective switches.
o
Disconnect the measuring equipment; restore the normal power supply connections.
o
Apply voltage to the power supply.
o
Close the protective switches for the voltage transformers.
o
Verify that the voltage phase rotation at the device terminals is correct. Note that the
device can be set for L1-L2-L3 rotation or L1-L3-L2 rotation under address
0235
PHASE SEQ.
in
P.System Data1
. See also Sub-section 6.1.1.
o
Open the protective switches for the voltage transformers and the power supply.
o
Check the trip circuits to the power system circuit breakers.
o
Check the close circuits to the power system circuit breakers.
o
Verify that the control wiring to and from other devices is correct.
o
Check the signalling connections.
o
Check the analog outputs (if available and used).
o
Close the protective switches to apply voltage to the power supply.
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...