Technical Data
10-5
7SA6 Manual
C53000-G1176-C156
Binary Outputs
Output relay (see also General Diagrams in Appendix A, Section A.2)
Number and Information
acc. to the order variant
(allocatable)
Alarm relay/Live Status contact
1
)
1 with NC contact or NO contact
(switch selectable)
Switching capability
MAKE
1000 W/VA
BREAK
30 VA
40 W resistive
25 W for L/R
≤
50 ms
Switching voltage
250 V
Permissible current per contact
5 A continuous
30 A for 0.5 s
Order Variant
UL-listed
NO
Contact
(normal)
1)
NO
Contact
(fast)
1)
NO/NC
(switch
selectable)
1)
NO
Contact
(high
–
speed)
1)
Power
Relay
2)
7SA610
∗
–
∗
A/E/J
x
7
–
1
–
–
7SA610
∗
–
∗
B/F/K
x
5
–
–
–
–
7SA6
∗
1
∗
–
∗
A/E/J
x
7
7
2
–
–
7SA6
∗
1
∗
–
∗
B/F/K
x
8
–
–
–
4
7SA6
∗
1
∗
–
∗
M/N/P
x
7
3
1
5
–
7SA6
∗
2
∗
–
∗
A/E/J
x
14
7
3
–
–
7SA6
∗
2
∗
–
∗
B/F/K
x
21
7
4
–
–
7SA6
∗
2
∗
–
∗
M/P/R
x
14
3
2
5
–
7SA6
∗
2
∗
–
∗
N/Q/S
x
21
3
3
5
–
7SA6
∗
2
∗
–
∗
C/G/L
x
11
–
–
–
8
7SA613
∗
–
∗
A
–
14
7
3
–
–
7SA613
∗
–
∗
M
–
14
3
2
5
–
Switching capability
MAKE
BREAK
1000 W/VA
30 VA
40 W ohmic
25 W/VA for L/R
≤
50 ms
1000 W/VA
1000 W/VA
–
–
–
–
Switching voltage
250 V
250 V
Permissible current per contact
/
pulse current
5 A permanent
30 A for 0.5 s
30 A for
0.5 s
Total permissible current
on common paths
5 A permanent
30 A for 0.5 s
–
–
Max. switching
capability for 30 s
for 48 V to
250 V
for 24 V
–
–
1000 W
500 W
Permissible relative closing time
–
1 %
Operating time, approx.
8 ms
5 ms
8 ms
1 ms
–
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...