Technical Data
10-34
7SA6 Manual
C53000-G1176-C156
10.13 Automatic Reclosure Function (optional)
Automatic
Reclosures
Number of reclosures
max. 8,
first 4 with individual settings
Operating modes
1-pole, 3-pole or 1-/3-pole
Control
with pick-up or trip command
Action times
0.01 s to 300.00 s;
∞
Initiation possible without pick-up
(steps 0.01 s)
and action time
Different dead times before
reclosure can be set for all
0.01 s to 1800.00 s;
∞
operating modes and cycles
(steps 0.01 s)
Dead times after evolving fault
0.01 s to 1800.00 s;
recognition
(steps 0.01 s)
Reclaim time after reclosure
0.50 s to 300.00 s
(steps 0.01 s)
Blocking time after dynamic
blocking
0.5 s
Blocking time after manual closing
0.50 s to 300.00 s ; 0
(steps 0.01 s)
Start signal monitoring time
0.01 s to 300.00 s
(steps 0.01 s)
Circuit-breaker supervision time
0.01 s to 300.00 s
(steps 0.01 s)
Adaptive Dead
Time (ADT)/
Reduced Dead
Time (RDT)/
Dead Line Check
Operating modes (ADT)
with voltage measurement or
with close command transmission
Action time
0.01 s to 300.00 s;
∞
Initiation possible without pick-up
(steps 0.01 s)
and action time
Maximum dead time
0.50 s to 3000.00 s;
∞
(steps 0.01 s)
Voltage measurement dead-line
or bus
2 V to 70 V (phase-to-earth)
(steps 1 V)
Voltage measurement live or bus
30 V to 90 V (phase-to-earth)
(steps 1 V)
Voltage supervision time for
dead / live line or bus
0.10 s to 30.00 s
(steps 0.01 s)
Time delay for close command
transmission
0.00 s to 300 s;
∞
(steps 0.01 s)
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...