Technical Data
10-39
7SA6 Manual
C53000-G1176-C156
Initiation
Conditions
For circuit breaker failure protection
single-pole tripping internal
three-pole tripping internal
single-pole tripping external
1
)
three-pole tripping external
1
)
three-pole tripping without current
1
)
1
) via binary inputs
Times
Pick-up time
approx. 7 ms with measured quantities
present prior to start,
approx. 20 ms after switch-on of
measured values
Drop-off time,internal
approx. 12 ms for sinusoidal measured
values,
(overshoot time)
approx
.
25 ms maximum
Delay times for all stages
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Tolerance
1 % of the set value or 10 ms
End Fault
Protection
With trip command transmission
to the remote end
Delay times for all stages
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Tolerance
1 % of the set value or 10 ms
Breaker Pole
Discrepancy
Monitoring
Initiation criterion
not all poles are closed or open
Monitoring time
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Tolerance
1 % of the set value or 10 ms
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...