Hardware and Connections
2-46
7SA6 Manual
C53000-G1176-C156-2
Figure 2-44
Optical communication interfaces with protective caps
Connections to
Optical
Communication
Interfaces with
ST–Connectors
Optical connector type:
ST–connector
Fibre type:
Multimode graded-index (“G”) optical fibre
G50/125 µm,
G62.5/125 µm,
G100/140 µm
Wavelength:
λ
= 820 nm (approximately)
Allowable bending radius:
For indoor cable
r
min
= 5 cm (2 in)
For outdoor cable r
min
= 20 cm (8 in)
Laser class 1 (acc. EN 60 825–1) is achieved with fibre type G50/125 µm and
G62.5/125 µm.
Optical Interfaces
(FC–Connector)
Optical communication interfaces with FC-connectors are provided with 1 channel or
1 to 2 channels. The ports are supplied with caps to protect the optical components
against dust or other contaminants. They can be removed from the interfaces.
The fibre-optic channels are located in an inclined housing. The inclined housing is at
the top side (channels “D” and “E”), see Figure 2-19).
Fibre-optic connections that are not needed are replaced by plastic studs.
Figure 2-45
Inclined housing with fibre-optic connections (channel D and E fitted)
2 channel
1 channel
Ch1
P-
Sl
av
e
Ch2
P-
M
as
te
r
UA
RT
Ch1
P-
Sl
av
e
AM
O
1 channel
Kanal B
Kanal D
Kanal C
Kanal E
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...