Appendix
B-20
7SA6 Manual
C53000-G1176-C156-2
3802
START
Fault Locator
Pickup
TRIP
Pickup
Start fault locator with
3805
Paral.Line Comp
Fault Locator
NO
YES
YES
Mutual coupling parall.line compensa-
tion
3806
Load Compensat.
Fault Locator
NO
YES
NO
Load Compensation
3811
Tmax OUTPUT
BCD
Fault Locator
0.10..180.00 sec
0.30 sec
Maximum output time via BCD
3901
FCT BreakerFail
Breaker Failure
ON
OFF
ON
Breaker Failure Protection is
3902
I> BF
Breaker Failure
0.05..20.00 A
0.10 A
Pick-up threshold I>
3903
1p-RETRIP (T1)
Breaker Failure
NO
YES
YES
1pole retrip with stage T1 (local trip)
3904
T1-1pole
Breaker Failure
0.00..30.00 sec;
∞
0.00 sec
T1, Delay after 1pole start (local trip)
3905
T1-3pole
Breaker Failure
0.00..30.00 sec;
∞
0.00 sec
T1, Delay after 3pole start (local trip)
3906
T2
Breaker Failure
0.00..30.00 sec;
∞
0.15 sec
T2, Delay of 2nd stage (busbar trip)
3907
T3-BkrDefective
Breaker Failure
0.00..30.00 sec;
∞
0.00 sec
T3, Delay for start with defective bkr.
3908
Trip BkrDefect.
Breaker Failure
NO
trips with T1-trip-signal
trips with T2-trip-signal
trips with T1 and T2-trip-sig-
nal
NO
Trip output selection with defective bkr
3909
Chk BRK CON-
TACT
Breaker Failure
NO
YES
YES
Check Breaker contacts
3921
End Flt. stage
Breaker Failure
ON
OFF
OFF
End fault stage is
3922
T-EndFault
Breaker Failure
0.00..30.00 sec;
∞
2.00 sec
Trip delay of end fault stage
3931
PoleDiscrepancy
Breaker Failure
ON
OFF
OFF
Pole Discrepancy supervision
3932
T-PoleDiscrep.
Breaker Failure
0.00..30.00 sec;
∞
2.00 sec
Trip delay with pole discrepancy
4001
FCT TripSuperv.
Trip Circuit Supervi-
sion
ON
OFF
OFF
TRIP Circuit Supervision is
4002
No. of BI
Trip Circuit Supervi-
sion
1..2
2
Number of Binary Inputs per trip circuit
4003
Alarm Delay
Trip Circuit Supervi-
sion
1..30 sec
2 sec
Delay Time for alarm
4201
Ther. OVERLOAD
Thermal Overload
OFF
ON
Alarm Only
OFF
Thermal overload protection
4202
K-FACTOR
Thermal Overload
0.10..4.00
1.10
K-Factor
4203
TIME CONSTANT
Thermal Overload
1.0..999.9 min
100.0 min
Time constant
4204
Θ
ALARM
Thermal Overload
50..100 %
90 %
Thermal Alarm Stage
4205
I ALARM
Thermal Overload
0.10..4.00 A
1.00 A
Current Overload Alarm setpoint
4206
CALC. METHOD
Thermal Overload
Theta Max
Average Theta
Theta from Imax
Theta Max
Method of Acquiring Temperature
4501
STATE PROT I 1
Protection Interface
(Port D+E)
ON
OFF
ON
State of protection interface 1
4502
CONNEC. 1 OVER Protection Interface
(Port D+E)
Direct connection with fibre
optic cabel
Communication converter
with 64 kBit/s
Communication converter
with 128 kBit/s
Communication converter
with 512 kBit/s
Direct connection with fibre
optic cabel
Connection 1 over
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Summary of Contents for siprotec 7SA6
Page 2: ...Siemens Aktiengesellschaft Book No C53000 G1176 C156 2 ...
Page 18: ...xviii 7SA6 Manual C53000 G1176 C156 2 ...
Page 32: ...Introduction 1 14 7SA6 Manual C53000 G1176 C156 2 ...
Page 82: ...Hardware and Connections 2 50 7SA6 Manual C53000 G1176 C156 2 ...
Page 119: ...SIPROTEC 4 Devices 4 25 7SA6 Manual C53000 G1176 C156 2 Figure 4 20 CFC Logic example ...
Page 190: ...Configuration 5 62 7SA6 Manual C53000 G1176 C156 2 ...
Page 652: ...Installation and Commissioning 8 78 7SA6 Manual C53000 G1176 C156 2 ...
Page 724: ...Technical Data 10 56 7SA6 Manual C53000 G1176 C156 ...
Page 800: ...Appendix A 76 7SA6 Manual C53000 G1176 C156 2 ...
Page 866: ...Appendix B 66 7SA6 Manual C53000 G1176 C156 2 ...