Functions
2.1 General
SIPROTEC, 7SC805, Manual
C53000-G1140-C380-1, Release date 05.2014
21
Special Features
Most settings are self-explanatory. The special cases are described in the following
At address
369
VT Con Type
, you can specify the connection type of the voltage inputs. If you are using normal
voltage transformers, select
CONVENTIONAL
.
With
459
Syscon MU Configuration
, you can define whether the communication parameter configured with
System configurator or not.
With
461
PhaseIndepRatio
, you can specify if the independent CT/VT ratio is supported for each channel.
Under address
700
GOOSE-Stop
, you can select whether the GOOSE function of the IEC 61850 protocol is
active or not. If
GOOSE-Stop
is set to
YES
, you can release the GOOSE function again via a binary input during
the operation.
Under address 357
SMV-Stop
, you can hide the information
>SMV-Stop
, which controlls the SMV telegram
sending function.
2.1.1.3
Settings
2.1.1.4
Information List
Addr.
Parameter
Setting Options
Default Setting
Comments
104
OSC. FAULT REC.
Disabled
Enabled
Disabled
Oscillographic Fault
Records
357
SMV-Stop
Yes
No
No
SMV-Stop
369
VT Con Type
Conventional
Cap. Volt.Meas.
Conventional
Voltage Connection Type
459
SysConMUConf
Enabled
Disabled
Enabled
MU Configuration via
IEC61850 System Con-
figurator
461
PhaseIndepRatio
Enabled
Disabled
Disabled
Phase Independent Ratio
640
Start image DD
image 1
image 2
image 3
image 4
image 5
image 6
image 1
Start image Default
Display
700
GOOSE-Stop
Yes
No
No
GOOSE-Stop
No.
Information
Type of In-
formation
Comments
-
>Light on
SP
>Back Light on
-
Reset LED
IntSP
Reset LED
-
DataStop
IntSP
Stop data transmission
-
Test mode
IntSP
Test mode
-
Feeder gnd
IntSP
Feeder GROUNDED