!PPENDIX
3*
6
# ' #
1600 UNDER VOLTAGE
1601 UNDERVOLTG
Undervoltage
OFF
[ ] off
ON
[ ] on
ALARM ONLY
[ ] Alarm only
1602 U< (PH-E)
Stage U< (phase-earth meas.)
min. 30
V
max. 120
¬¬¬¬
1603 U< (PH-PH)
Stage U< (phase-phase meas.)
min. 30
V
max. 120
¬¬¬¬
1604 r (PH-E)
Reset ratio r (ph-e) of u/v stage U<
min. 1.05
max. 3.00
¬¬¬¬
1605 r (PH-PH)
Reset ratio r (ph-ph) of u/v stage U<
min. 1.05
max. 3.00
¬¬¬¬
1606 T-U<
Delay time T-U< of u/v stage U<
min. 0.00
s
max. 60.00/Ô
¬¬¬¬
1607 START.CRIT
Starting criterion of u/v protection
OFF
[ ] off
ON
[ ] on
1608 SC I<
Stage I< for starting crit., u/v prot.
min. 0.05
I/In
max. 1.00
¬¬¬¬
1609 T-SC
Active time for starting criterion u/v
min. 0.00
s
max. 60.00
¬¬¬¬
1610 U<< (PH-E)
Stage U<< (phase-earth meas.)
min. 30
V
max. 120
¬¬¬¬
1611 U<<(PH-PH)
Stage U<< (phase-phase meas.)
min. 30
V
max. 120
¬¬¬¬
1612 T-U<<
Delay time T-U<< of u/v stage U<
min. 0.00
s
max. 60.00/Ô
¬¬¬¬
1620 C CRIT U/V
Current criterion of undervoltage prot.
ON
[ ] on
OFF
[ ] off