!PPENDIX
3*
6
# ' #
2806 nw
Maximum permissible number of warm-starts
min. 1
max. 4
¬¬¬¬
2807 nc-nw
Difference between no. of cold and warm-starts
min. 1
max. 2
¬¬¬¬
2808 kÏ-FACTOR
Factor for tau during standstill
min. 1
max. 10
¬¬¬¬
¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬
2900 MEAS.VALUE SUPERVISION
2901 SYM.Uthres
Symmetry threshold for voltage monitoring
min. 10
V
max. 100/Ô
¬¬¬¬
2902 SYM.Fact.U
Symmetry factor for voltage monitoring
min. 0.58
max. 0.90
¬¬¬¬
2903 SYM.Ithres
Symmetry threshold for current monitoring
min. 0.10
I/In
max. 1.00/Ô
¬¬¬¬
2904 SYM.Fact.I
Symmetry factor for current monitoring
min. 0.10
max. 0.95
¬¬¬¬
2905 SUM.Ithres
Summation threshold for current monitoring
min. 0.05
I/In
max. 2.00/Ô
¬¬¬¬
2906 SUM.Fact.I
Factor for current summation monitoring
min. 0.00
max. 0.95
¬¬¬¬
2930 LIMIT IL1
Limit IL1
min. 0.10
I/In
max. 25.00
¬¬¬¬
2931 LIMIT IL2
Limit IL2
min. 0.10
I/In
max. 25.00
¬¬¬¬
2932 LIMIT IL3
Limit IL3
min. 0.10
I/In
max. 25.00
¬¬¬¬
2933 LIMIT IE
Limit IE
min. 0.05
I/In
max. 25.00
¬¬¬¬
2934 LIMIT IL<
Limit of minimal phase current
min. 0.10
I/In
max. 4.00
¬¬¬¬