!PPENDIX
3*
6
# ' #
7512 LOC/REM SEL
Local / remote selection
W/O CODEWD
[ ] without codeword
WITH CW
[ ] with codeword
7520 T-FB CB
Feed back time of circuit breaker T-FB
min. 1
s
max. 600/Ô
¬¬¬¬
7522 T-EXT CB
Trip cmd extension time for CB
min. 0.0
s
max. 10.0
¬¬¬¬
7524 T-SFB END
End of feedback supervision time
STOPS TRIP CMD
[ ] stops trip command
STOPS NOT TRIP C [ ] does not stop trip
7525 T-DWI
Wrong indication delay time
min. 0
s
max. 60/Ô
¬¬¬¬
7598 SWITCH AUTH
Switching authorization
LOCAL
[ ] LOCAL
LOCAL/REMOTE
[ ] LOCAL/REMOTE
VIA BI
[ ] via binary input
LOCKED
[ ] locked
7599 SWITCH AUTH
Switching authorization
LOCAL
[ ] LOCAL
REMOTE
[ ] REMOTE
VIA BI
[ ] via binary input
LOCKED
[ ] locked
¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬
7800 SCOPE OF FUNCTIONS
7812 CHARAC. PH
Characteristic O/C protection phases
DEFINITE TIME
[ ] Definite time
INV. TIME IEC
[ ] Inverse time (IEC)
INV. TIME ANSI
[ ] ANSI inv
USER CHARACTER. [ ] User characteristics
7813 CHARAC. E
Characteristic O/C protection earth
DEFINITE TIME
[ ] Definite time
INV. TIME IEC
[ ] Inverse time (IEC)
INV. TIME ANSI
[ ] ANSI inv
USER CHARACTER. [ ] User characteristics
7814 O/C DIR.PH
O/C - Directional phase inst/time
DEFINITE TIME
[ ] Definite time
INV. TIME IEC
[ ] Inverse time (IEC)
INV. TIME ANSI
[ ] ANSI inv
USER CHARACTER. [ ] User characteristics
NON-EXIST
[ ] Non-existent
7815 O/C DIR. E
O/C - Directional earth inst/time
DEFINITE TIME
[ ] Definite time
INV. TIME IEC
[ ] Inverse time (IEC)
INV. TIME ANSI
[ ] ANSI inv
USER CHARACTER. [ ] User characteristics
NON-EXIST
[ ] Non-existent