Functions
2.5 Single-Phase Overcurrent Protection
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
139
2.5.5
Settings
The table indicates region-specific default settings. Column C (configuration) indicates the corresponding sec-
ondary nominal current of the current transformer.
2.5.6
Information List
Addr.
Parameter
C
Setting Options
Default Setting
Comments
2701
50 1Ph
OFF
ON
OFF
50 1Ph
2702
50 1Ph-2 PICKUP
1A
0.05 .. 35.00 A;
∞
0.50 A
50 1Ph-2 Pickup
5A
0.25 .. 175.00 A;
∞
2.50 A
2703
50 1Ph-2 PICKUP
0.003 .. 1.500 A;
∞
0.300 A
50 1Ph-2 Pickup
2704
50 1Ph-2 DELAY
0.00 .. 60.00 sec;
∞
0.10 sec
50 1Ph-2 Time Delay
2705
50 1Ph-1 PICKUP
1A
0.05 .. 35.00 A;
∞
0.20 A
50 1Ph-1 Pickup
5A
0.25 .. 175.00 A;
∞
1.00 A
2706
50 1Ph-1 PICKUP
0.003 .. 1.500 A;
∞
0.100 A
50 1Ph-1 Pickup
2707
50 1Ph-1 DELAY
0.00 .. 60.00 sec;
∞
0.50 sec
50 1Ph-1 Time Delay
No.
Information
Type of In-
formation
Comments
5951
>BLK 50 1Ph
SP
>BLOCK 50 1Ph
5952
>BLK 50 1Ph-1
SP
>BLOCK 50 1Ph-1
5953
>BLK 50 1Ph-2
SP
>BLOCK 50 1Ph-2
5961
50 1Ph OFF
OUT
50 1Ph is OFF
5962
50 1Ph BLOCKED
OUT
50 1Ph is BLOCKED
5963
50 1Ph ACTIVE
OUT
50 1Ph is ACTIVE
5966
50 1Ph-1 BLK
OUT
50 1Ph-1 is BLOCKED
5967
50 1Ph-2 BLK
OUT
50 1Ph-2 is BLOCKED
5971
50 1Ph Pickup
OUT
50 1Ph picked up
5972
50 1Ph TRIP
OUT
50 1Ph TRIP
5974
50 1Ph-1 PU
OUT
50 1Ph-1 picked up
5975
50 1Ph-1 TRIP
OUT
50 1Ph-1 TRIP
5977
50 1Ph-2 PU
OUT
50 1Ph-2 picked up
5979
50 1Ph-2 TRIP
OUT
50 1Ph-2 TRIP
5980
50 1Ph I:
VI
50 1Ph: I at pick up