Functions
2.19 Synchronization Function
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
322
170.2027 25 V1> V2<
OUT
25 Condition V1>V2< fulfilled
170.2028 25 V1< V2>
OUT
25 Condition V1<V2> fulfilled
170.2029 25 V1< V2<
OUT
25 Condition V1<V2< fulfilled
170.2030 25 Vdiff ok
OUT
25 Voltage difference (Vdiff) okay
170.2031 25 fdiff ok
OUT
25 Frequency difference (fdiff) okay
170.2032 25
α
diff ok
OUT
25 Angle difference (alphadiff) okay
170.2033 25 f1>>
OUT
25 Frequency f1 > fmax permissible
170.2034 25 f1<<
OUT
25 Frequency f1 < fmin permissible
170.2035 25 f2>>
OUT
25 Frequency f2 > fmax permissible
170.2036 25 f2<<
OUT
25 Frequency f2 < fmin permissible
170.2037 25 V1>>
OUT
25 Voltage V1 > Vmax permissible
170.2038 25 V1<<
OUT
25 Voltage V1 < Vmin permissible
170.2039 25 V2>>
OUT
25 Voltage V2 > Vmax permissible
170.2040 25 V2<<
OUT
25 Voltage V2 < Vmin permissible
170.2050 V1 =
MV
V1 =
170.2051 f1 =
MV
f1 =
170.2052 V2 =
MV
V2 =
170.2053 f2 =
MV
f2 =
170.2054 dV =
MV
dV =
170.2055 df =
MV
df =
170.2056 d
α
=
MV
dalpha =
170.2090 25 V2>V1
OUT
25 Vdiff too large (V2>V1)
170.2091 25 V2<V1
OUT
25 Vdiff too large (V2<V1)
170.2092 25 f2>f1
OUT
25 fdiff too large (f2>f1)
170.2093 25 f2<f1
OUT
25 fdiff too large (f2<f1)
170.2094 25
α
2>
α
1
OUT
25 alphadiff too large (a2>a1)
170.2095 25
α
2<
α
1
OUT
25 alphadiff too large (a2<a1)
170.2096 25 FG-Error
OUT
25 Multiple selection of func-groups
170.2097 25 Set-Error
OUT
25 Setting error
170.2101 25-1 OFF
OUT
Sync-group 1 is switched OFF
170.2102 >BLK 25 CLOSE
SP
>BLOCK 25 CLOSE command
170.2103 25 CLOSE BLK
OUT
25 CLOSE command is BLOCKED
170.2332 Sync f syn
OUT
Sync:Synchronization cond. f syn
No.
Information
Type of In-
formation
Comments
www
. ElectricalPartManuals