Functions
2.20 Temperature Detection via RTD Boxes
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
329
9092A
RTD 9 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 9: Location
9093
RTD 9 STAGE 1
-50 .. 250 °C;
∞
100 °C
RTD 9: Temperature Stage 1
Pickup
9094
RTD 9 STAGE 1
-58 .. 482 °F;
∞
212 °F
RTD 9: Temperature Stage 1
Pickup
9095
RTD 9 STAGE 2
-50 .. 250 °C;
∞
120 °C
RTD 9: Temperature Stage 2
Pickup
9096
RTD 9 STAGE 2
-58 .. 482 °F;
∞
248 °F
RTD 9: Temperature Stage 2
Pickup
9101A
RTD10 TYPE
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Not connected
RTD10: Type
9102A
RTD10 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD10: Location
9103
RTD10 STAGE 1
-50 .. 250 °C;
∞
100 °C
RTD10: Temperature Stage 1
Pickup
9104
RTD10 STAGE 1
-58 .. 482 °F;
∞
212 °F
RTD10: Temperature Stage 1
Pickup
9105
RTD10 STAGE 2
-50 .. 250 °C;
∞
120 °C
RTD10: Temperature Stage 2
Pickup
9106
RTD10 STAGE 2
-58 .. 482 °F;
∞
248 °F
RTD10: Temperature Stage 2
Pickup
9111A
RTD11 TYPE
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Not connected
RTD11: Type
9112A
RTD11 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD11: Location
9113
RTD11 STAGE 1
-50 .. 250 °C;
∞
100 °C
RTD11: Temperature Stage 1
Pickup
9114
RTD11 STAGE 1
-58 .. 482 °F;
∞
212 °F
RTD11: Temperature Stage 1
Pickup
9115
RTD11 STAGE 2
-50 .. 250 °C;
∞
120 °C
RTD11: Temperature Stage 2
Pickup
9116
RTD11 STAGE 2
-58 .. 482 °F;
∞
248 °F
RTD11: Temperature Stage 2
Pickup
Addr.
Parameter
Setting Options
Default Setting
Comments
www
. ElectricalPartManuals
. com