Technical Data
4.10 Negative Sequence Protection 46-TOC
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
501
Trip Time Curves acc. to ANSI
Tolerances
It can be selected one of the represented trip time characteristic curves in the figures 4-8 and 4-9 each on the
right side of the figure.
The trip times for
I
2
/
I
2p
≥
20 are identical to those for
I
2
/
I
2p
= 20.
Pickup Threshold
Approx. 1.10·
I
2p
Pickup Threshold
I
2p
3 % of setting value or 10 mA for
I
Nom
= 1 A
or 50 mA with
I
Nom
= 5 A
Time for 2
≤
I
/
I
2p
≤
20
5 % of reference (calculated) value + 2 % current tolerance,
respectively 30 ms
www
. ElectricalPartManuals