Appendix
A.8 Settings
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
640
5303
FUSE FAIL RESID
Measurem.Superv
1A
0.10 .. 1.00 A
0.10 A
Residual Current
5A
0.50 .. 5.00 A
0.50 A
5307
I> BLOCK
Measurem.Superv
0.10 .. 35.00 A;
∞
1.00 A
I> Pickup for block FFM
5310
BLOCK PROT.
Measurem.Superv
NO
YES
YES
Block protection by FFM
5401
FCT 81 O/U
81 O/U Freq.
OFF
ON
OFF
81 Over/Under Frequency Pro-
tection
5402
Vmin
81 O/U Freq.
10 .. 150 V
65 V
Minimum required voltage for op-
eration
5403
81-1 PICKUP
81 O/U Freq.
40.00 .. 60.00 Hz
49.50 Hz
81-1 Pickup
5404
81-1 PICKUP
81 O/U Freq.
50.00 .. 70.00 Hz
59.50 Hz
81-1 Pickup
5405
81-1 DELAY
81 O/U Freq.
0.00 .. 100.00 sec;
∞
60.00 sec
81-1 Time Delay
5406
81-2 PICKUP
81 O/U Freq.
40.00 .. 60.00 Hz
49.00 Hz
81-2 Pickup
5407
81-2 PICKUP
81 O/U Freq.
50.00 .. 70.00 Hz
59.00 Hz
81-2 Pickup
5408
81-2 DELAY
81 O/U Freq.
0.00 .. 100.00 sec;
∞
30.00 sec
81-2 Time Delay
5409
81-3 PICKUP
81 O/U Freq.
40.00 .. 60.00 Hz
47.50 Hz
81-3 Pickup
5410
81-3 PICKUP
81 O/U Freq.
50.00 .. 70.00 Hz
57.50 Hz
81-3 Pickup
5411
81-3 DELAY
81 O/U Freq.
0.00 .. 100.00 sec;
∞
3.00 sec
81-3 Time delay
5412
81-4 PICKUP
81 O/U Freq.
40.00 .. 60.00 Hz
51.00 Hz
81-4 Pickup
5413
81-4 PICKUP
81 O/U Freq.
50.00 .. 70.00 Hz
61.00 Hz
81-4 Pickup
5414
81-4 DELAY
81 O/U Freq.
0.00 .. 100.00 sec;
∞
30.00 sec
81-4 Time delay
5415A
DO differential
81 O/U Freq.
0.02 .. 1.00 Hz
0.02 Hz
Dropout differential
5421
FCT 81-1 O/U
81 O/U Freq.
OFF
ON f>
ON f<
OFF
81-1 Over/Under Frequency Pro-
tection
5422
FCT 81-2 O/U
81 O/U Freq.
OFF
ON f>
ON f<
OFF
81-2 Over/Under Frequency Pro-
tection
5423
FCT 81-3 O/U
81 O/U Freq.
OFF
ON f>
ON f<
OFF
81-3 Over/Under Frequency Pro-
tection
5424
FCT 81-4 O/U
81 O/U Freq.
OFF
ON f>
ON f<
OFF
81-4 Over/Under Frequency Pro-
tection
6001
S1: RE/RL
P.System Data 2
-0.33 .. 7.00
1.00
S1: Zero seq. compensating
factor RE/RL
6002
S1: XE/XL
P.System Data 2
-0.33 .. 7.00
1.00
S1: Zero seq. compensating
factor XE/XL
6003
S1: x'
P.System Data 2
0.0050 .. 15.0000
Ω
/mi
0.2420
Ω
/mi
S1: feeder reactance per mile: x'
6004
S1: x'
P.System Data 2
0.0050 .. 9.5000
Ω
/km
0.1500
Ω
/km
S1: feeder reactance per km: x'
6005
S1: Line angle
P.System Data 2
10 .. 89 °
85 °
S1: Line angle
6006
S1: line length
P.System Data 2
0.1 .. 650.0 Miles
62.1 Miles
S1: Line length in miles
6007
S1: Line length
P.System Data 2
0.1 .. 1000.0 km
100.0 km
S1: Line length in kilometer
6011
S2: RE/RL
P.System Data 2
-0.33 .. 7.00
1.00
S2: Zero seq. compensating
factor RE/RL
6012
S2: XE/XL
P.System Data 2
-0.33 .. 7.00
1.00
S2: Zero seq. compensating
factor XE/XL
6013
S2: x'
P.System Data 2
1A
0.0050 .. 15.0000
Ω
/mi
0.2420
Ω
/mi
S2: feeder reactance per mile: x'
5A
0.0010 .. 3.0000
Ω
/mi
0.0484
Ω
/mi
6014
S2: x'
P.System Data 2
1A
0.0050 .. 9.5000
Ω
/km
0.1500
Ω
/km
S2: feeder reactance per km: x'
5A
0.0010 .. 1.9000
Ω
/km
0.0300
Ω
/km
6015
S2: Line angle
P.System Data 2
10 .. 89 °
85 °
S2: Line angle
6016
S2: line length
P.System Data 2
0.1 .. 650.0 Miles
62.1 Miles
S2: line length in miles
6017
S2: Line length
P.System Data 2
0.1 .. 1000.0 km
100.0 km
S2: Line length in kilometer
6021
S3: RE/RL
P.System Data 2
-0.33 .. 7.00
1.00
S3: Zero seq. compensating
factor RE/RL
6022
S3: XE/XL
P.System Data 2
-0.33 .. 7.00
1.00
S3: Zero seq. compensating
factor XE/XL
6023
S3: x'
P.System Data 2
1A
0.0050 .. 15.0000
Ω
/mi
0.2420
Ω
/mi
S3: feeder reactance per mile: x'
5A
0.0010 .. 3.0000
Ω
/mi
0.0484
Ω
/mi
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments
www
. ElectricalPartManuals