Appendix
A.8 Settings
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
645
6446
T SYNC-DELAY
SYNC function 4
0.00 .. 60.00 sec
0.00 sec
Release delay at synchronous
conditions
6450
dV SYNCHK V2>V1
SYNC function 4
0.5 .. 50.0 V
5.0 V
Maximum voltage difference
V2>V1
6451
dV SYNCHK V2<V1
SYNC function 4
0.5 .. 50.0 V
5.0 V
Maximum voltage difference
V2<V1
6452
df SYNCHK f2>f1
SYNC function 4
0.01 .. 2.00 Hz
0.10 Hz
Maximum frequency difference
f2>f1
6453
df SYNCHK f2<f1
SYNC function 4
0.01 .. 2.00 Hz
0.10 Hz
Maximum frequency difference
f2<f1
6454
d
α
SYNCHK
α
2>
α
1
SYNC function 4
2 .. 80 °
10 °
Maximum angle difference
alpha2>alpha1
6455
d
α
SYNCHK
α
2<
α
1
SYNC function 4
2 .. 80 °
10 °
Maximum angle difference
alpha2<alpha1
7001
FCT 50BF
50BF BkrFailure
OFF
ON
OFF
50BF Breaker Failure Protection
7004
Chk BRK CONTACT
50BF BkrFailure
OFF
ON
OFF
Check Breaker contacts
7005
TRIP-Timer
50BF BkrFailure
0.06 .. 60.00 sec;
∞
0.25 sec
TRIP-Timer
7006
50BF PICKUP
50BF BkrFailure
1A
0.05 .. 20.00 A
0.10 A
50BF Pickup current threshold
5A
0.25 .. 100.00 A
0.50 A
7007
50BF PICKUP IE>
50BF BkrFailure
1A
0.05 .. 20.00 A
0.10 A
50BF Pickup earth current
threshold
5A
0.25 .. 100.00 A
0.50 A
7101
FCT 79
79M Auto Recl.
OFF
ON
OFF
79 Auto-Reclose Function
7103
BLOCK MC Dur.
79M Auto Recl.
0.50 .. 320.00 sec; 0
1.00 sec
AR blocking duration after
manual close
7105
TIME RESTRAINT
79M Auto Recl.
0.50 .. 320.00 sec
3.00 sec
79 Auto Reclosing reset time
7108
SAFETY 79 ready
79M Auto Recl.
0.01 .. 320.00 sec
0.50 sec
Safety Time until 79 is ready
7113
CHECK CB?
79M Auto Recl.
No check
Chk each cycle
No check
Check circuit breaker before AR?
7114
T-Start MONITOR
79M Auto Recl.
0.01 .. 320.00 sec;
∞
0.50 sec
AR start-signal monitoring time
7115
CB TIME OUT
79M Auto Recl.
0.10 .. 320.00 sec
3.00 sec
Circuit Breaker (CB) Supervision
Time
7116
Max. DEAD EXT.
79M Auto Recl.
0.50 .. 1800.00 sec;
∞
100.00 sec
Maximum dead time extension
7117
T-ACTION
79M Auto Recl.
0.01 .. 320.00 sec;
∞
∞
sec
Action time
7118
T DEAD DELAY
79M Auto Recl.
0.0 .. 1800.0 sec;
∞
1.0 sec
Maximum Time Delay of Dead-
Time Start
7127
DEADTIME 1: PH
79M Auto Recl.
0.01 .. 320.00 sec
0.50 sec
Dead Time 1: Phase Fault
7128
DEADTIME 1: G
79M Auto Recl.
0.01 .. 320.00 sec
0.50 sec
Dead Time 1: Ground Fault
7129
DEADTIME 2: PH
79M Auto Recl.
0.01 .. 320.00 sec
0.50 sec
Dead Time 2: Phase Fault
7130
DEADTIME 2: G
79M Auto Recl.
0.01 .. 320.00 sec
0.50 sec
Dead Time 2: Ground Fault
7131
DEADTIME 3: PH
79M Auto Recl.
0.01 .. 320.00 sec
0.50 sec
Dead Time 3: Phase Fault
7132
DEADTIME 3: G
79M Auto Recl.
0.01 .. 320.00 sec
0.50 sec
Dead Time 3: Ground Fault
7133
DEADTIME 4: PH
79M Auto Recl.
0.01 .. 320.00 sec
0.50 sec
Dead Time 4: Phase Fault
7134
DEADTIME 4: G
79M Auto Recl.
0.01 .. 320.00 sec
0.50 sec
Dead Time 4: Ground Fault
7135
# OF RECL. GND
79M Auto Recl.
0 .. 9
1
Number of Reclosing Cycles
Ground
7136
# OF RECL. PH
79M Auto Recl.
0 .. 9
1
Number of Reclosing Cycles
Phase
7137
Cmd.via control
79M Auto Recl.
(Setting options depend
on configuration)
None
Close command via control
device
7138
Internal SYNC
79M Auto Recl.
(Setting options depend
on configuration)
None
Internal 25 synchronisation
7139
External SYNC
79M Auto Recl.
YES
NO
NO
External 25 synchronisation
7140
ZONE SEQ.COORD.
79M Auto Recl.
OFF
ON
OFF
ZSC - Zone sequence coordina-
tion
7150
50-1
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
50-1
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments