Functions
6-60
7SJ63 Manual
C53000-G1140-C120-1
6.3.2.6
Information List for Directional Ground Overcurrent Protection
1609
67N–TOC T– DIAL
0.50 ~ 15.00
5.00 sec
Time dial setting, ANSI
X
1610
67N–TOC RESET
immediate
disk emulation
Disk emulation
Characteristics of 67N-
TOC dropout
X
X
1611
67N-TOC IEC
Normal Inverse
Very Inverse
Extremely Inverse
Long Inverse
Normal Inverse
Characteristic curve (IEC)
X
X
X
X
1612
67N–TOC ANSI
Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inverse
Extremely Inverse
Definite Inverse
Very inverse
Characteristic curve (AN-
SI)
X
X
X
X
X
X
X
1613
MANUALCLOSE-
MODE
67N-2 instanta-
neously
67N-1 instanta-
neously
67N-TOC instanta-
neously
Inactive
67N-2 instanta-
neously
Selection of high speed
tripping element when
manual closing feature is
used
X
X
X
X
X
1614
67N active
Always
with 79 active
Always
Criteria for operation of
67N-2 element
X
X
X
X
X
1615
Normal Load
(Torque angle of
dir. fct)
Inductive (135°)
Resistive (90°)
Capacitive (45°)
Inductive
((135°)
Angle of the directional lim-
it line
X
X
X
X
X
1616
67N Direction
Forward
Reverse
Forward
Directional orientation of
the 67N elements
X
X
X
X
X
1630
M.of PU TD
67N-TOC user defined
characteristic curve values
X
X
1631
I/IEp Rf T/TEp
67N-TOC reset user de-
fined curve values
X
Addr.
LCD-Text
Setting options
Default Setting
Comments
Configuration
D
e
finit
e Ti
m
e
Only
IEC
Curv
e
A
N
SI
Curve
U
s
er Def
ined Pick
up
U
s
er def
.
Res
et
F#
LCD-Text
Comment
2656
67N OFF
67N/67N-TOC switched OFF
2657
67N BLOCKED
67N/67N-TOC is BLOCKED
2658
67N ACTIVE
67N/67N-TOC is ACTIVE
2646
67N-2 picked up
67N-2 picked up