Functions
6-66
7SJ63 Manual
C53000-G1140-C120-1
Addr.
Setting
Setting Options
Default Setting
Comment
Configuration
Defini
te T
im
e
Only
IEC Curve
A
N
SI
Cur
ve
Us
er Defined P
ickup
Us
er def.
Reset
1701
COLD LOAD
PICKUP
OFF
ON
OFF
Dyn. Cold Load Setting Adj. On/Off
X X X X X
1702
Start Condition
No Current
Breaker Contact
No Current
Dyn. Cold Load Setting Adj. Arming
Condition
X X X X X
1703
CB Open Time
0 ~21600 s
3600 s
Dyn. Cold Load Setting Adj. Arming
Time
X X X X X
1704
Active Time
1 ~21600 s
3600 s
Dyn. Cold Load Setting Adj. Active
Time
X X X X X
1705
Stop Time
1 ~600 s
600 s
Dyn. Cold Load Setting Adj. Active
Time With Normal I
X X X X X
Addr.
CLP–Setting
Setting Options
Default
Setting
Addr.
Normal Setting
Configuration
Defini
te Time
Only
IEC Curve
AN
SI
Curv
e
Use
r Defined P
ickup
Use
r def.
Reset
1801
50c-2 PICKUP
0.50 ~ 175.00 A
50.00 A
1202
50-2 PICKUP
X X X X X
1802
50c-2 DELAY
0.00 ~ 60.00 sec.
0.00 sec.
1203
50-2 DELAY
X X X X X
1803
50c-1 PICKUP
0.50 ~ 175.00 A
10.00 A
1204
50-1 PICKUP
X X X X X
1804
50c-1 DELAY
0.00 ~ 60.00 sec.
0.30 sec.
1205
50-1 DELAY
X X X X X
1805
51c PICKUP
0.50 ~ 20.00 A
7.50 A
1207
51 PICKUP
X X X X
1806
51c TIME DIAL
0.05 ~ 3.20 sec.
0.50 sec.
1208
51 TIME DIAL, IEC
X
X X
1807
51c TIME DIAL
0.5 ~ 15.00
5.00 sec.
1209
51 TIME DIAL, ANSI
X
Addr.
Setting
Setting Options
Default
Setting
Addr.
Normal Setting
Configuration
Defi
nite
Time Only
IE
C Curve
AN
SI Curv
e
User
Defined P
ickup
User
def.
Reset
1901 50Nc-2 PICKUP
0.25 ~ 175.00 A
35.00 A
1302
50N-2 PICKUP
X X X X X
1902 50Nc-2 DELAY
0.00 ~ 60.00 sec.
0.00 sec.
1303
50N-2 DELAY
X X X X X
1903 50Nc-1 PICKUP
0.25 ~ 175.00 A
7.50 A
1304
50N-1 PICKUP
X X X X X
1904 50Nc-1 DELAY
0.00 ~ 60.00 sec.
0.30 sec.
1305
50N-1 DELAY
X X X X X