Technical Data
10-39
7SJ63 Manual
C53000-G1140-C120-1
Reset
– Automatic
Time of day adjustable (in minutes).
Time frame and starting time
adjustable (in days, 1 to 365 days, and
∞
).
Reset
– Manual
Using binary input
Using keypad
Using communication
Min/Max Values for Current
I
a
, I
b
, I
c
, I
1
(positive sequence)
Min/Max Values for Voltages
Va-n, Vb-n, Vc-n, V
1
(positive sequence)
Va-b, Vb-c, Vc-a, Vn
Min/Max Values for Power/ Other
S, P, Q, cos
ϕ
, Frequency
Min/Max Values for Averages
I
Admd
, I
Bdmd
, I
Cdmd
, I
1dmd
(positive sequence)
(LOG of Primary Values)
S
d
, P
d
, Q
d
Measured Values
Supervision
Current Asymmetry
I
max
/I
min
> I - balance factor, for I > I - bal-
ance limit. Factor and limit are adjustable.
Voltage Asymmetry
V
max
/V
min
> V - balance factor,for V > V -
balance limit. Factor and limit are
adjustable.
Current Sum
| i
a
+i
b
+i
c
+[k
n
· i
n
] | > I - sum
threshold value, adjustable.
k
n
= CT
n
ratio / CT
phase
ratio
Current Phase Sequence
Clockwise (ABC)/ counter-clockwise (ACB)
Voltage Phase Sequence
Clockwise (ABC)/ counter-clockwise (ACB)
Limit Value Monitor
I
a
> Limit value I
A dmd
>
I
b
> Limit value I
B dmd
>
I
c
> Limit value I
C dmd
>
I
1
> Limit value I
1 dmd
>
I
L
< Limit value 37-1
cos
ϕ
< Lower limit value |cos
ϕ
|<
P > Limit value |P
dmd
|>
Q > Limit value |Q
dmd
|>
S > Limit value |S
dmd
|>
Pressure < Lower limit value Press<
Temperature > Limit value Temp>
Trip Log)
Recording of indication of the last 8 power system faults
Recording of indication of the last 3 power system ground faults
Time Stamping
Resolution for Event Log
1 ms
(Operational Messages)
Resolution for Trip Log (Fault Records)
1 ms
Time Deviation (Internal Clock)
Maximum 0.01%
Buffer Battery
Lithium Battery, 3 V / 1 Ah, type CR 1/2 AA
Self-discharging time > 5 years
Message “Fail Battery” if
battery charge is low
www
. ElectricalPartManuals
. com