Routine Checks and Maintenance
9-7
7SJ63 Manual
C53000-G1140-C120-1
o
Remove the covers on the front panel and loosen the screws that are securing the
front panel.
o
Carefully pull off the front panel.
o
Place the new battery into the clamp fixture as shown in Figure 9-2.
Figure 9-2
Rear view of the front panel (1/2 case) showing battery location
o
Carefully replace the front panel. Fasten the panel to the case with the screws.
o
Replace the covers.
o
Close the protective switches to apply voltage to the power supply.
o
After the device is operating, data saved in DIGSI
®
4 can be loaded back into the de-
vice.
If the internal system clock is not automatically synchronized via a serial interface,
then the clock should be set at this point. Refer to Sub-section 7.2.1 if assistance is
needed to set the clock.
+
+
–
–
G2
Battery
Warning!
The used battery contains Lithium. Do not throw the battery into the trash!
Do not reverse the polarity! Do not completely discharge! Do not throw the bat-
tery into a fire! Explosion hazard!
www
. ElectricalPartManuals