Circuit Breaker Failure Protection
129
7SS52 V4 Manual
C53000-G1176-C182-3
The parameter
(
XX15/C
U
) is used to select the operating mode for the
breaker failure protection in the bay unit. The parameter setting depends on the pro-
tection concept in use.
the breaker failure protection will be deactivated.
the I> query mode is activated.
With setting
the TRIP repetition with subsequent I> query mode
is activated.
the unbalancing mode is activated.
the TRIP repetition with subsequent unbalancing
mode is activated.
the breaker failure protection will be provided by an external
device.
(
XX16/CU
) is used to activate and deactivate the low-current
mode.
the low-current mode is activated.
the low-current mode is deactivated.
The low-current mode can be used together with the following settings:
•
XX14/CU
) with and without supervision
•
XX15/CU
) Breaker failure operating mode, in the settings:
−
I
>
query
−
TRIP repetition/I
>
query:
−
Unbalancing
−
TRIP repetition/Unbalancing
The low-current mode cannot be used together with the following setting
of the parameter
(
XX15/CU
).
Note
:
With the mode
I> Query
the dropout time (measuring window) of the breaker failure pro-
tection of 25 ms must be considered for setting the times
T-BF-1P
(
XX20/CU
)
and
T-BF-mP
(
XX12/CU
)
.
With the mode
BZ Unbalance
the dropout time is 2 ms and need not be taken into con-
sideration for setting the times
T-BF-1P
(
XX20/CU
)
and
T-BF-mP
(
XX21/CU
).