End Fault Protection
139
7SS52 V4 Manual
C53000-G1176-C182-3
5.4.3
Setting Notes
(
XX26/CU
) is used to delay processing of the circuit
breaker OPEN status for special treatment of the coupler currents and for the end fault
protection.
If the bay is configured as a feeder, the parameter
XX29/CU
) is
used to activate and deactivate the end fault protection. For coupler bays the setting
of this parameter is not relevant.
5.4.4
Settings for the Central Unit
5.4.5
List of Information from the Central Unit
5.4.6
List of Information from the Bay Unit
Addr.
Setting Title
Setting Options
Default Setting
Comments
118
I> BF
0.10 .. 2.00 I / In
0.50 I / In
Current threshold for BF
119
I> BF-EF
0.05 .. 2.00 I / In
0.25 I / In
Current threshold for BF - EF
120
T-BF-1P
0.05 .. 10.00 s
0.25 s
Time delay for BF with 1-pole fault
121
T-BF-mP
0.05 .. 10.00 s
0.25 s
Time delay for BF with multi-pole
faults
125
T-TRIP repeat
0.00 .. 10.00 s
0.12 s
Time delay for TRIP repeat
126
T-CB open
0.00 .. 10.00 s
0.00 s
Time delay for CB open
129 End
Fault
Prot
ON
OFF
OFF End
fault
protection
FNo.
Alarm
Comments
10477
CZ release
Check zone released
10478
>EF charact.
>Earth fault characteristic active
FNo.
Alarm
Comments
7617
>CB OFF
>Circuit breaker open
7618
>CB man.close
>Circuit breaker manual close
7623
>CB ON
>Circuit breaker closed
7644
End-Flt. Trip
End fault protection: Trip phase L123