Power System Data of the Bay Unit
187
7SS52 V4 Manual
C53000-G1176-C182-3
T TRIP
The parameter
T TRIP
(
1141/BU
)
is used to set the minimum time which must elapse
before the TRIP command is reset. This time is started with the output of a TRIP com-
mand.
5.15.3 Settings of the Central Unit
5.15.4 Settings of the Bay Unit
Note
The parameter
T TRIP (1141/BU
) can only be set with the bay unit running in
stand-alone mode.
The value entered in the central unit for the parameter
(
) is not
affected by this.
With the bay unit linked to the central unit, the setting of this parameter is transmitted
from the central unit to the bay units. The local setting in the bay units is overwritten.
Addr.
Setting Title
Setting Options
Default Settings
Comments
5104
FREQUENCY
50 Hz
60 Hz
50 Hz
Nominal frequency
6106
Tmin TRIP
0.01 .. 32.00 sec
0.15 sec
Minimum duration of TRIP com-
mand
Addr.
Setting Title
Setting Options
Default Settings
Comments
1101
CT STARPNT
TOWARDS LINE
TOWARDS BUSBAR
TOWARDS LINE
Current transformer polarity lies
1105
In PRIMARY
10 .. 50000 A
400 A
Primary rated current
1141
T TRIP
0.01 .. 32.00 sec
0.15 sec
Minimum TRIP command dura-
tion