Control During Operation
226
7SS52 V4 Manual
C53000-G1176-C182-3
Click
Device
→
Trigger test fault recording...
on the menu bar. The window Fault
Record Length opens (Figure 6-15, page 226).
Enter the desired fault record length and click
OK
. The fault recording starts. The
fault record length must be within the specified limits.
Figure 6-15 Fault Record Length dialog box in DIGSI
6.3.2
Blocking
6.3.2.1
Blocking the TRIP Command
The TRIP commands can be blocked for the entire protection or busbar-selectively.
With the TRIP command blocked all device-internal protection functions (central unit,
bay unit) remain active. However, a TRIP command is not initiated i.e., the TRIP com-
mand relays configured in the bay units are not activated. This is useful e.g., during
the commissioning phase.
Blocking the TRIP
command -
entire protection
The blocking of the TRIP command for the entire protection is blocked with the tagging
“
“ (
FNo. 10441/CU
) or via a binary input “
FNo.
/
CU
). The blocking is indicated by the annunciation “
FNo.
).
Note
You can also trigger the fault recording via the operator panel of the central unit. If you
want to know more on this topic, please read the System Description /1/.
Caution!
If the busbar is to be blocked, make sure that it is an isolated bar, i.e. there are no
closed sectionalizing isolators or sectionalizer forks provided. While being blocked,
no switching operations are permitted on the blocked bar. The non-blocked busbar
sections are not affected by any restrictions to the operational management.