Controlling Device Functions
229
7SS52 V4 Manual
C53000-G1176-C182-3
from the PC
with DIGSI
To block the TRIP command via the
central unit
(PC linked to central unit) proceed
as follows:
Click
Control
in the navigation window.
Double-click
Tagging
in the function selection. The Tagging window opens (see
To block the TRIP command, click the command button
ON
in the corresponding
row. To reset the blocking of the TRIP command, click the command button
OFF
.
Next a security prompt takes place.
While the Tagging window is opened, there will be no further security prompts when
you change the tagging status.
Click
Yes
to apply the command. The blocking of the TRIP command can be pro-
tected by the password for switching/selecting/updating. If you have activated this
password, you will be prompted to enter it before the command is executed since a
connection was first established. A dialog box opens for this purpose.
Enter the correct password in the box named
Password
and then click
OK
. If the
password is wrong, you will receive an error message. When the password is cor-
rect, the command will be executed.
Figure 6-17 Tagging window in DIGSI
Note
You can also block the TRIP command via the operator panel of the central unit. If you
want to know more on this topic, please read the System Description /1/.