Commissioning
277
7SS52 V4 Manual
C53000-G1176-C182-3
7.3.6
Switching the Test Mode and the Transmission Block On and OFF.
If the central unit is linked to a central control or storage facility you can influence in
some of the available protocols the information which are transmitted to the control
center (see table “Protocol Dependent Functions” in the Appendix).
When the test
Test mode
is switched on, the annunciations sent by a SIPROTEC4
device to the control center are marked with an additional test bit, so that they can be
recognized as not being annunciations of real faults. Furthermore it can be determined
by activating the
Transmission block
that no annunciations at all are transmitted via
the system port during a test mode.
To switch on the test mode click in the menu bar DIGSI Device Configuration
Device
→
Test mode
.
To activate the transmission block click in the menu bar DIGSI Device Configuration
Device
→
Transmission Block
.
www
. ElectricalPartManuals