Technical Data
318
7SS52 V4 Manual
C53000-G1176-C182-3
9.2.10 Circuit Breaker Failure Protection
Control modes
One or two-channel initiation
Modes of operation
Individually selectable per feeder:
−
I
>
query
−
TRIP repeat (1/3-phase) with
I
>
query
−
Unbalancing (1-stage CBF)
−
Unbalancing with TRIP repeat
(1-/3-phase, 2-stage CBF)
−
TRIP by external CBF
protection (tripping via isolator
replica of busbar protection)
−
plus for each mode
(except for TRIP by external
CBF):
low-current mode
−
plus for modes with
TRIP repeat:
pulse mode
Setting ranges
Overcurrent
I / I
N
0.10 to 2.00 (in steps of 0.01)
0.05 to 2.00 (Earthfault characteristic)
Stabilizing factor
k
0.05 to 0.80 (in steps of 0.01)
Time delay for
unbalancing / I>query
0.05 to 10.00 s (in steps of 0.01)
Time delay for
TRIP repeat
0.00 to 10.00 s (in steps of 0.01)
Drop-off times
Mode “unbalancing”
Approx. 2 ms
Mode “I>query”
Approx.25 ms
Definite time (backup protection)
Approx.25 ms
Tolerances
Current
5 % of setting value or 50 mA
k factor
5 % of setting value
Time
5 % of setting value or 50 ms