Technical Data
324
7SS52 V4 Manual
C53000-G1176-C182-3
EMC tests for
immunity
(type tests)
Standards:
IEC 60255-6 and -22, (product standards)
EN 61000-6-2 (generic standard)
VDE 0435 Section 301, DIN VDE 0435-110
– High-frequency test
2.5 kV (peak); 1 MHz;
τ
=
15
µ
s;
IEC 60255-22-1, Class
III
and
400 pulses per s; test duration 2 s;
VDE 0435 Section 303, Class III
R
I
=
200
Ω
– Attenuated oscillation
2.5 kV (Peak Value), polarity alternating
IEC 60694, IEC 61000-4-12
100 kHz, 1 MHz, 10 MHz and 50 MHz,
R
I
=
200
Ω
– Discharge of static electricity
8 kV contact discharge;
IEC 60 55-22-2, Class
IV
15 kV air discharge; both polarities;
and IEC 61000-4-2, Class
IV
150 pF; R
I
=
330
Ω
– Irradiation with HF field,
10 V/m; 80 MHz to 1000 MHz;
frequency sweep
10 V/m; 800 MHz to 960 MHz;
IEC 60255-22-3, Class III
80% AM; 1kHz
IEC 61000-4-3, Class III
– Irradiation with HF field,
single frequencies IEC 60255-22-3,
10 V/m 80/160/450/900 MHz;
IEC 61000-4-3, amplitude-modulated r80 % AM 1 kHz; duty cycle > 10 s
Class III:
– Radiated Electromagnetic Interference 35 V/m; 25 MHz to 1000 MHz
IEEE Std C37.90.2
– Fast transient disturbance/Burst
PE conductor: 1 kV / 5 kHz;
IEC 60255-22-4 and
all circuits: 4 kV / 2.5 kHz;
IEC 61000-4-4 Class
IV
5 / 50 ns; 5 kHz;
burst duration
=
15 ms;
repetition rate 300 ms;
both
polarities;
R
I
=
50
Ω
; test duration 1 min
– High-energy surge voltages (SURGE), Impulse: 1.2/50
µ
s
IEC 61000-4-5 installation Class 3
Auxiliary voltage
common mode: 2 kV; 12
Ω
; 9
µ
F
diff. mode: 1 kV; 2
Ω
; 18
µ
F
measuring inputs, binary inputs
common mode: 2 kV; 42
Ω
; 0.5
µ
F
and relay outputs
diff. mode: 1 kV; 42
Ω
; 0.5
µ
F
– HF on lines
10 V (r.m.s. value);
IEC 60255-22-6
150 kHz to 80 MHz; 80 %; 1 kHz; AM;
IEC 61000-4-6 Class
III
R
I
=
150
Ω
– Power system-frequency
30 A/m continuously;
magnetic field
300 A/m for 3 s; 50 Hz;
IEC 61000-4-8
IEC 255-6 Class IV