List of information - Central Unit
379
7SS52 V4 Manual
C53000-G1176-C182-3
10490
>Blocking back-up breaker
fail.prot. BU (>Block BF of BU)
BF-Protection
SP
on
off
*
*
LED BI
BO
194
167
1
Yes
10491
Blocking back-up breaker
fail.prot. BU (Block BF of BU)
BF-Protection
IntSP
on
off
*
*
LED
BO
194
168
1
Yes
10492
Back-up breaker fail.prot. of BU
blocked (Blkd BF of BU)
BF-Protection
OUT
on
off
*
*
LED
BO
194
169
1
Yes
10493
>Blocking O/C protection of BU
(>Block O/C BU)
Protec. general
SP
on
off
*
*
LED BI
BO
194
195
1
Yes
10494
Blocking O/C protection of BU
(Block O/C BU)
Protec. general
IntSP
on
off
*
*
LED
BO
194
196
1
Yes
10495
O/C protection of BU blocked
(Blkd O/C BU)
Protec. general
OUT
on
off
*
*
LED
BO
194
197
1
Yes
10496
BF protection BZ blocked (group
alarm) (BF BZ blkd G)
BF-Protection
OUT
on
off
*
*
LED
BO
10497
Trip command BZ blocked (group
alarm) (TRIP BZ blkd G)
BB Protection
OUT
on
off
*
*
LED
BO
30053
Fault recording is running (Fault
rec. run.)
Osc. Fault Rec.
OUT
*
*
*
LED
BO
009.0100
Failure EN100 Modul (Failure
Modul)
EN100-Modul 1
IntSP
on
off
*
*
LED
BO
009.0101
Failure EN100 Link Channel 1
(Ch1) (Fail Ch1)
EN100-Modul 1
IntSP
on
off
*
*
LED
BO
009.0102
Failure EN100 Link Channel 2
(Ch2) (Fail Ch2)
EN100-Modul 1
IntSP
on
off
*
*
LED
BO
176.1061
$00 out of service (OutOfServ
$00)
BU@
OUT
on
off
*
*
LED
BO
195
6
1
Yes
176.1062
$00 isolator maintenance (Maint-
en. $00)
BU@
OUT
on
off
*
*
LED
BO
195
3
1
Yes
176.1063
$00 failure (Failure $00)
BU@
OUT
on
off
*
*
LED
BO
195
8
1
Yes
176.1071
Trip repeat $00 phase L1
(TripRep$00 L1)
BU@
OUT
*
on
*
LED
BO
195
10
2
Yes
176.1072
Trip repeat $00 phase L2
(TripRep$00 L2)
BU@
OUT
*
on
*
LED
BO
195
11
2
Yes
176.1073
Trip repeat $00 phase L3
(TripRep$00 L3)
BU@
OUT
*
on
*
LED
BO
195
12
2
Yes
176.1081
No release of TRIP command
$00 (noTripRel $00)
BU@
OUT
*
on
*
LED
BO
195
15
2
Yes
176.1082
Breaker fail/Transfer trip $00
(TrnsfTrip $00)
BU@
OUT
*
on
*
LED
BO
195
16
2
Yes
176.1091
Timing error BF input $00 L1 (BF-
BIErr$00 L1)
BU@
OUT
on
off
*
*
LED
BO
195
18
1
Yes
176.1092
Timing error BF input $00 L2 (BF-
BIErr$00 L2)
BU@
OUT
on
off
*
*
LED
BO
195
19
1
Yes
176.1093
Timing error BF input $00 L3 (BF-
BIErr$00 L3)
BU@
OUT
on
off
*
*
LED
BO
195
20
1
Yes
176.1094
Timing error BF input $00 3pole
(BFBIErr$00 3P)
BU@
OUT
on
off
*
*
LED
BO
195
21
1
Yes
176.1101
Timing error BF release $00 1P
(BFRlErr$00 1P)
BU@
OUT
on
off
*
*
LED
BO
195
23
1
Yes
176.1102
Timing error BF release $00 3P
(BFRlErr$00 3P)
BU@
OUT
on
off
*
*
LED
BO
195
24
1
Yes
176.1104
Timing error BF pulse $00 (BF-
PulsErr $00)
BU@
OUT
on
off
*
*
LED
BO
195
17
1
Yes
176.1110
$01 Isolator $02 ($01 $02)
1)
BU@
DP
*
*
*
LED
BO
195
25
1
Yes
FNo.
Description
Function
Type
ofIn-
for-
matio
n
Log-Buffer
Configurable in Matrix
IEC 60870-5-103
Eve
n
t Log On/
O
ff
Trip (Faul
t) Lo
g On/
O
ff
G
roun
d Faul
t
Log
On/
O
ff
M
a
rk
e
d
in Os
c
ill
. Rec
o
rd
LED
Bi
nary I
nput
Fu
nc
ti
on Key
Binar
y
Outpu
t
Chatter Block
ing
Ty
p
e
Inf
o
rm
a
tion No.
D
a
ta
Un
it
General
In
te
rr
ogation
www
. ElectricalPartManuals
. com