Operation of SIPROTEC Devices from the Operator Panel
41
7SS52 V4 Manual
C53000-G1176-C182-3
3.6.3
Setting Addresses in the Bay Unit
The central unit can only communicate with the bay units if the setting of the substation
address, the feeder address and the device address in each bay unit matches the cor-
responding IEC addresses in the DIGSI Manager. You can for this initialize the bay
units with the DIGSI software or, as an alternative, set the addresses on the operator
panel of the bay unit.
To set the device address on the operator panel of a bay unit:
Use the navigation keys
or
to navigate to the menu item
7200 PC/SYSTEM
INTERFACES
, and the navigation key
to go on to the submenu for the parameter
7201 DEVICE ADD
.
(see Figure 3-5, page 42).
Press the
key and enter the password
F3F1F3F1F3F1
.
Confirm with the
key. The password is accepted, and the message
Passw. ac-
cepted
appears in the display.
Confirm 2 more times with the
key. The display now changes into edit mode.
Set the correct device address using the
or the
key.
Press the
key.
Use the navigation keys
or
to navigate to the menu itemt
END OF CODEWORD
OPERATION
.
Press the
key. The message
SAVE NEW SETTINGS
appears.
Press the
key again. The message
NEW SETTINGS SAVED
appears and the
device reset. The device address that you have entered is now accepted and
stored.
Note
The parameter
7201 DEVICE ADD.
is only displayed with the bay unit running in
stand-alone mode.