Marshalling
73
7SS52 V4 Manual
C53000-G1176-C182-3
4.6
Marshalling
In the previous step you have assigned the configured bay units to the bay units cre-
ated in the Device Manager.
Next you will allocate information items to the input and output components of 7SS52
V4 such as binary inputs and binary outputs or LEDs. Information items can be indi-
cations and measured values.
You will not only determine the allocation itself but also the type of the allocation.
An indication may for example be allocated to an LED in latched or unlatched mode.
Also user-defined logic function can be the source of and the destination for informa-
tion items. The assignment of information items to sources and destinations is called
marshalling.
4.6.1
Marshalling Information Items of the Central Unit
4.6.1.1
Allocable Information
Binary inputs
The D-CPU communication module features 5 binary inputs (BI 1 to 5).
The EAZ input/output module features 7 binary inputs (BI 6 to 12).
The binary inputs are freely allocable. The can be activated with or without voltage.
Event data and binary input data are pre-allocated (see Table A-22, page 395).
The Chapter A.9, page 373 gives an overview of all possible indications with their func-
tion number (
FNo.
).
Binary outputs and
LED indicators
The central unit features 16 alarm relays and 32 LED indicators.
Any number of annunciations can be marshalled to a binary output (group annuncia-
tion). The most common group annunciations with their own function number are al-
ready available in the system (see Chapter A.11, page 389).
Group annunciations that are not available by default are created by allocating the dif-
ferent function numbers to a relay and/or to an LED. Existing allocations may have to
be deleted beforehand.
Each annunciation may be allocated to up to 10 relays or LEDs.
The presetting of the signal relays and of the LEDs is identical upon delivery and can
be looked up in the tables A-23, page 395 and A-24, page 396.
The Chapter A.9, page 373 gives an overview of all possible indications with their func-
tion number (
FNo.
).
Note
Allocate the indication “
“(
FNo. 10478/CU
) for the earth fault charac-
teristic to the binary input 1 to 5 since these binary inputs process by 1 to 2 ms faster
than the binary inputs 6 to 12.