Functions
178
7SS52 V4 Manual
C53000-G1176-C182-3
5.11
Integrated Operation of the Bay Unit
5.11.1 Functional Description
This section summarizes those parameters by which you choose the UI language of
the bay unit and specify the measured values to be displayed in the “standby” display.
5.11.2 Setting Notes
LANGUAGE
The parameter
LANGUAGE
(
7101/BU
) is used to set the UI language of the bay unit.
With the setting
DEUTSCH
the menus in the display of the bay unit appear in German.
With the setting
ENGLISH, FRANCAIS, ESPANOL, ITALIANO, PYCCK.
the
menus in the display of the bay unit appear in the respective target language.
OPER.1st L.
OPER.2nd L.
OPER.3rd L.
OPER.4th L.
The parameters
OPER.1st L.
(
7120/BU
),
OPER.2nd L.
(
7122/BU
),
OPER.3rd L.
(
7124/BU
) and
OPER.4th L.
(
7126/BU
) are used to select the
measured value which will be displayed in the 1st, 2nd, 3rd and 4th line of the “stand-
by” display in 4-line mode.
You can choose from:
•
The currents of the three phases IL1, IL2, IL3
•
The earth fault current IE
•
The differential currents of the three phases IdL1, IdL2, IdL3
•
The stabilizing currents of the three phases IsL1, IsL2, IsL3
OPER.1st L.
OPER.2nd L.
OPER.3rd L.
OPER.4th L.
The parameters
OPER. 1st L.
(
7121/BU
),
OPER.2nd L.
(
7123/BU
),
OPER.3rd L.
(
7125/BU
) and
OPER.4th L.
(
7127/BU
) are used to select the
mode of display for the measured value in the 1st, 2nd, 3rd and 4th line of the “stand-
by” display in 4-line mode.
With setting
PRIMARY
, the measured value will be displayed as primary value, i.e.
with the unit Ampere (A).
With setting
SECONDARY
, the measured value will be displayed as secondary value,
i.e. in percent of the rated current.
With the setting
NORMALIZED
, the measured value will be displayed as normalized
value, i.e. referring to the same reference current. The reference current is set in the
plant configuration.
Note
The parameter
LANGUAGE
(
7101/BU
) can only be set with the bay unit running in
stand-alone mode.
The value entered in the central unit for the parameter
5111A/CU
)
is not affected by this.
With the bay unit linked to the central unit, the setting of this parameter is transmitted
from the central unit to the bay units. The local setting in the bay units is overwritten.