Reading Out Information
213
7SS52 V4 Manual
C53000-G1176-C182-3
Displaying event
buffers with DIGSI
To display event buffers of the
central unit
(PC linked to central unit) proceed as fol-
lows:
Open the central unit in the DIGSI Manager.
Click the folder
Online
in the navigation window of the DIGSI Device Configuration.
This will open the directory containing the operating functions of the device (see
Figure 6-1, page 213).
Double-click
Annunciations
. The function selection now shows the individual
event buffers. The individual event buffers will be described in more detail in the fol-
lowing subsections.
Figure 6-1 Annunciation groups in the DIGSI Device Configuration
To display event buffers of a single
bay unit
(PC linked to central unit or bay unit) pro-
ceed as follows:
Open the corresponding bay unit in the DIGSI Manager.
Click
Annunciation
. The function selection shows the submenu for Annunciation
and Measurement.
Double-click the entry
Annunciation
. The Select annunciation window shows the
individual event buffers. The individual event buffers will be described in more detail
in the following subsections.
Light-emitting di-
odes on the front
panel
The green LED labelled “RUN” lights permanently during normal operation.
The red LED labelled “ERROR” indicates that the processor system has detected an
internal error. The device is not ready when the red LED flashes during operation.
Chapter 8, page 289 provides information on how to proceed in such a case.
The other LEDs on the device indicate the annunciations which are allocated accord-
ing to Chapter 4, page 45. After you have allocated the LED, write down its meaning
on the labeling strip.
Stored indications for LEDs (e.g., protection trip) can be deleted via the pushbutton
or via DIGSI. This pushbutton serves also as functional check for the LEDs. All
LEDs must be lit while you apply this pushbutton.