Control During Operation
214
7SS52 V4 Manual
C53000-G1176-C182-3
Output relays
Annunciations which are allocated to the potential-free output relays according to
Chapter 4, page 45 can be output as latched annunciations. The memories of the out-
put relays can also be reset by applying the
button.
6.2.1.1
Operational Annunciations
Operational annunciations are information items which the device produces during op-
eration. Up to 200 operational events (central unit) and up to 50 operational events
(bay units) are stored in the device in chronological order. When the maximum capac-
ity of the memory has been reached, the oldest event will be erased.
The appendix contains a tabular list with all available operational events and their ex-
planation. Only the relevant annunciation will be displayed in the concrete situation. It
is also indicated whether the annunciation is only coming (
C
for events) or whether it
is coming and going (
C/G
for states).
from the PC
with DIGSI
To read out operational events of the
central unit
(PC linked to central unit) proceed
as follows:
Click
Event log
. A list appears in the data window (right section of the window),
Double-click an entry in the list view. The corresponding contents of the annunciation
group is displayed in another window (Figure 6-3, page 215).