Controlling Device Functions
237
7SS52 V4 Manual
C53000-G1176-C182-3
Click an entry in the list and click
Run...
.
Enter the correct password in the box named
Password
and then click
OK
. If the
password is wrong, you will receive an error message. When the password is cor-
rect, the circuit breaker test will be executed.
6.3.5
Reset Blocking
6.3.5.1
Reset Blocking of Differential Current Supervision
6310/CU
) and
(
CU
) to specify the behaviour of the protection for a pick-up of the differential cur-
rent supervision (Chapter 5.5.1.8, page 144).
The blocking is reset by applying “
“ or via binary input “
(
BI-FNo. 6/CU
) in the central unit.
from the PC
with DIGSI
To reset the blocking of the differential current supervision at the
central unit
(PC
linked to central unit) proceed as follows:
Click
Control
in the navigation window.(see Figure 6-24, page 237).
Double-click
Rest blocking of diff.-current superv.
in the function selection. The
resetting of the blocking can be protected by the password for the parameter set. If
you have activated this password, you will be prompted to enter it before the com-
mand is executed. A dialog box opens for this purpose.
Enter the correct password in the box named
Password
and then click
OK
. If the
password is wrong, you will receive an error message. When the password is cor-
rect, the blocking will be reset.
Figure 6-24 Reset blocking of differential current supervision using DIGSI
Note
) and
(
CU
) are set to
, the function
Reset blocking of diff.-current
superv.
is not available.