2.19 Auxiliary Functions
193
7ST6 Manual
E50417-G1176-C251-A3
2.19.3.2 Setting Notes
Readout/Set-
ting/Resetting
The SIPROTEC
®
4 System Description describes how to read out the statistical
counters using the device front panel or DIGSI
®
. Setting or resetting of these statistical
counters takes place under the menu item
Annunciation
->
STATISTIC
by overwrit-
ing the counter values displayed.
2.19.3.3 Information List
No.
Information
Type of In-
formation
Comments
1000
# TRIPs=
VI
Number of breaker TRIP commands
1008
Σ
(I/In)^2=
VI
Sum of fault currents (I/In)^2
13851
Σ
It=
VI
Summation of measured It values
13852
Σ
I2t=
VI
Summation of measured I2t values
13853
Last It=
VI
Last It value measured
13854
Last I2t=
VI
Last I2t value measured
13870
AR 1st cycle=
VI
AR Number reclosure attempts 1st cycle
13871
AR >1st cycle=
VI
AR Number reclosure attempts >1st cycle
13925
MAX I=
VI
Max. fault current
13926
Last I=
VI
Last current interrupted by CB
13927
Σ
I=
VI
Summation interrupted primary currents
16006
Resid.Endu.=
VI
Residual Endurance
16011
mechan.TRIP=
VI
Number of mechanical Trips