4 Technical Data
260
7ST6 Manual
E50417-G1176-C251-A3
Fibre optic cable (FO)
FO connector type
ST connector
Connection for panel flush-mounted
housing
Rear panel, mounting location „B“
Connection for panel surface-mounted
housing
In console housing on bottom
Optical wavelength
λ
= 820 nm
Laser Class 1 according to EN 60825-1/-2 Using glass fibre 50/125
µ
m or using glass
fibre 62.5/125
µ
m
Permissible optical link signal attenuation Max. 8 dB, with glass fibre 62.5/125
µ
m
Channel distance
Max. 1.5 km (5,000 ft.)
Character idle state
Selectable: factory setting „Light off“
Profibus RS 485 (FMS and DP)
Connection for panel flush-mounted
housing
Rear panel, mounting location „B“ 9-pin D-
subminiature female connector
Connection for panel surface-mounted
housing
9-pin D-subminiature female connector in
console housing on the bottom
Test voltage
500 V; 50 Hz
Transmission speed
Up to 12 MBaud
Channel distance
1,000 m (3,300 ft.) at
≤
93.75 kBd
500 m (1,150 ft.) at
≤
187.5 kBd
200 m (660 ft.) at
≤
1.5 MBaud
100 m (330 ft.) at
≤
12 MBaud
Profibus FO (FMS and DP)
FO connector type
ST-connector single ring / double ring ac-
cording to the order for FMS; for DP only
double ring available
Connection for panel flush-mounted
housing
Rear panel, mounting location „B“
Connection for panel surface-mounted
housing
Please use version with Profibus RS485 in
the console housing at the housing bottom
as well as separate electrical/optical con-
verter
Transmission speed
Conversion by means of external OLM
1)
up to 1.5 MBaud
≥
500 kBaud for normal version
Recommended speed:
> 500 kBd
Optical wavelength
λ
= 820 nm
Laser Class 1 according to EN 60825-1/-2 Using glass fibre 50/125
µ
m or using glass
fibre 62.5/125
µ
m
Permissible optical link signal attenuation Max. 8 dB, with glass fibre 62.5/125
µ
m
Transmission distance between two
modules with redundant optical ring topol-
ogy and optical fibre 62.5/125 m
2 m (6.6 ft.) with plastic fibre
500 kB/s max. 1.6 km (5,250 ft.)
1500 kB/s 530 m (1,738 ft.)
Character idle state (status for "No charac-
ter")
Light OFF
Max. number of modules in optical rings
with 500 kB/s or 1500 kB/s
41