4.2 Distance Protection
267
7ST6 Manual
E50417-G1176-C251-A3
Times
Shortest trip time
40 ms at 16.7 Hz
35 ms at 25 Hz
25 ms at 50/60 Hz
Dropout time
80 ms at 16.7 Hz
60 ms at 25 Hz
30 ms at 50/60 Hz
SI Time Man.Cl Operating time for manual close
signal
0.01 s to 30.00 s
Increments 0.01 s
Stage timers: T1, T2, T2K, T2L, T3K, T3L, T1b, T1L
Can be set separately for each timer
0.00 s to 30.00 s;
∞
Increments 0.01 s
Time expiry tolerances
1 % of setting value or 10 ms
The set times are pure delay times