4 Technical Data
282
7ST6 Manual
E50417-G1176-C251-A3
General Limits
Device-Specific Limits
Additional Limits
1)
When the limit is exceeded, an error indication is output by the device. Consequently, the
device starts monitoring. The red ERROR-LED lights up.
Description
Limit
Comment
Maximum number of all CFC charts considering all task
levels
32
When the limit is exceeded, an error in-
dication is output by the device. Conse-
quently, the device starts monitoring.
The red ERROR LED lights up. Reduce
the number of CFC charts until they are
below the limit again.
Maximum number of all CFC charts considering one task
level
16
Only error indication
(evolving fault in processing procedure)
Maximum number of all CFC inputs considering all charts
400
When the limit is exceeded, an error in-
dication is output by the device. Conse-
quently, the device starts monitoring.
The red ERROR LED lights up. Reduce
the number of CFC inputs until they are
below the limit again.
Maximum number of inputs of one chart for each task level
(number of unequal information items of the left border per
task level)
400
Only error indication; here the number of
elements of the left border per task level
is counted. Since the same information
is indicated at the border several times,
only unequal information is to be count-
ed.
Maximum number of reset-resistant flipflops
D_FF_MEMO
50
No error indication
(evolving error in processing procedure)
Description
Limit
Comment
Maximum number of synchronous changes of chart inputs
per task level
50
When the limit is exceeded, an error in-
dication is output by the device. Conse-
quently, the device starts monitoring.
The red ERROR-LED lights up.
Maximum number of chart outputs per task level
150
Additional Limits
for the Following 4 CFC Blocks:
Task Level
Maximum Number of Modules in the Task Levels
LONG_TIMER
TIMER
CMD_CHAIN
D_FF_MEMO
MV_PROC
18
50
PLC1_PROC
9
20
PLAN_BEARB
S_BEARB
www